Gensets Technical Data:
Unit model
Generator set model
DC-500GF
Power (KW)
Prime power
Kilowatt (KW)
500
Power (KVA)
Kilovolt-ampere (KVA)
625
Voltage
Output voltage
Volts/Hertz
400/230V
speed
Rated speed
Rotation (r/min)
1500
Phase count/line count
phases /lines
/
3-phase 4-wire
noise
Noise limit
Decibel (db)
≤ 117
current
Maximum output current
Ampere (A)
900
fuel consumption
Fuel Consumption at 100%
g/(kW·h)
≤ 198
size
Gensets Dimensions
Millimeter (MM)
3600*1500*1850
weight
Gensets weight
Kilogram (KG)
3900
Engine Technical Data
Engine model
6M33D633E200
Engine brand
Weichai
power
Rated power
633kw
Engine type
Vertical, inline, water-cooled, four-
stroke
Fuel injection form
Injection Type
Direct Injection
intake method
Intake way
Turbocharged Inter-cooled
Number of engine cylinders
No. of Cylinders
6
Cylinder bore and stroke
piston stroke
150*185
Total displacement
Displacement
Liters (L)
19.6
connection type
Connection Type
≤ 1
Startup method
Starting way
24V DC start
speed regulation method
Governor Type
Electronic speed regulation
Overall dimensions
Engine dimension
Engine Dry Weight
Specification of alternator
Generator model
YHB-500
Generator brand
Shanghai Stanford
rated power
number of
bearings
Number ofBearing
Single bearing
Protection level
Protection Grade
IP22
excitation method
Exciter Type
Brushless self-motivation
Pressure regulating method
Voltage regulation mode
AVR Automatic voltage regulation
insulation class
Insulation Class
H
Telephone
interference
coefficient
Telephone interference Factor(TIF)
≤50
harmonic factor
Telephone harmonic factor(THF)
≤2%
Steady-state
voltage regulation
Voltage Regulation, Steady State
≤±0.5%
Transient voltage regulation
Transient State Voltage
≤+20%~-15%
Voltage fluctuation rate
frequency
regulation ratio
frequency regulation,Steady State
Transient
regulation
Transient frequency regulation
≤+10%~-7%
Frequency
fluctuation rate
Frequency fluctuation